Project Title | 12 KV Pad Mounted Distribution Transformers (WHS 825, 11135 and 11176) |
Physical Address | View project details and contacts |
City, State (County) | High Point, NC (Guilford County) |
Category(s) | Single Trades |
Sub-Category(s) | Electric |
Contracting Method | Competitive Bids. |
Project Status | Request for Proposals (RFPs) |
Bids Due | View project details and contacts |
Estimated Value | |
Plans Available from | Municipal Agency |
Owner | View project details and contacts |
Architect | View project details and contacts |
Description | High Voltage: 7.2 KV/12.47 KV GROUNDED WYE Low Voltage: 208Y/120 High Voltage Bushings: Six (6) Bushing wells for Loop feed dead front operation which will accept the Elastimold 1602 A3R load break feed-thru insert and/or equivalent. Bushing Arrangement: ANSI C57.12.26 FIG 6a for 14.4 KV, Loop Feed on High Voltage side. Minimum height of lowest bushing to centerline -- 27 inches. Low Voltage Bushings: Four (4) Hole NEMA spade bushings up to 300 KVA Six (6) Hole NEMA WITH CABLE SUPPORT spade bushings for transformers 500 KVA and 750 KVA . Eight (8) Hole NEMA WITH CABLE SUPPORT for 1000 KVA or greater. |
||
Details |
|
||
Bidder's List | View project details and contacts | ||
Prospective Bidders | View project details and contacts | ||
Project Documents |