Similar Projects
Last Updated | 04/15/2022 12:32 AM |
Project Title | Simeon HS- Chiller Repairs |
Physical Address | View project details and contacts |
City, State (County) | Chicago, IL 60620 (Cook County) |
Category(s) | Single Trades |
Sub-Category(s) | HVAC |
Contracting Method | Competitive Bids. |
Project Status | Results |
Bids Due | View project details and contacts |
Estimated Value | |
Plans Available from | |
Owner | View project details and contacts |
Architect | View project details and contacts |
Description | CHILLER # 1 Remove and Replace Control Fuses. CIRCUIT # 3 Pump Out and Remove Oil from Circuit. Pump In New Oil into Circuit. Remove and Replace Slide Transducer. Perform Nitrogen Leak Test and Repair Soderable Leaks. Place Vacuum on the System and Leave Overnight for a Tight Seal. Remove and Replace Filter Driers. Charge Circuit with 285 LBS of 134 A Refrigerant. CIRCUIT # 1 Pump Out and Remove Oil from Circuit. Pump In New Oil into Circuit. Perform Nitrogen Leak Test and Repair Soderable Leaks. Place Vacuum on the System and Leave Overnight for a Tight Seal. Remove and Replace Site Glass Remove and Replace Filter Driers. Charge Circuit with 285 LBS of 134 A Refrigerant. CHILLER # 2 Remove and Replace Control Fuses. CIRCUIT # 3 Pump Out Oil and Remove Oil from Circuit. Pump In New Oil into Circuit. Remove and Replace Slide Transducer. Perform Nitrogen Leak Test and Repair Soderable Leaks. Place Vacuum on the System and Leave Overnight for a Tight Seal. Remove and Replace Filter Driers. Charge with 285 LBS of 134 A Refrigerant. CIRCUIT # 1 Pump Out Oil and Remove Oil from Circuit. Pump In New Oil into Circuit. Charge with 60 LBS of 410 A Refrigerant. |
||
Details |
|
||
Bidder's List | View project details and contacts | ||
Prospective Bidders | View project details and contacts | ||
Project Documents |
Engineered Spec Sheet Architectural Plans Other Documents |