Similar Projects
Last Updated | 02/03/2022 01:23 PM |
Project Title | Duplex Pump Control Panel |
Physical Address | View project details and contacts |
City, State (County) | Jacksonville, NC (Onslow County) |
Category(s) | Single Trades |
Sub-Category(s) | Electric |
Contracting Method | Competitive Bids. |
Project Status | Request for Quotations |
Bids Due | View project details and contacts |
Estimated Value | |
Plans Available from | Municipal Agency |
Owner | View project details and contacts |
Architect | View project details and contacts |
Description | Duplex Pump Control Panel for Brinson Creek Pump Station. The voltage is three phase wye 277/480 volts, the neutral terminates in the ATS. The pumps are Fairbanks Morse, model no. 5” D5436MV, HP: 118; RPM: 1800; Volts: 460; Amps: 139.4. The following specifications apply: a. NEMA 4X Hoffman stainless steel enclosure with three point latches and inner doors. Enclosure width not to exceed 48”. b. Main control panel circuit breaker and individual pump circuit breakers, Square D brand. c. Main power distribution block. Distribution lugs on the load end of the MB may be used in lieu of MPDB. d. Surge Protector, Square D brand. e. Phase monitor, Symcom brand f. Four float control system logic. g. Intrinsically Safe Module, Symcom brand h. Lag pump Time Delay Relay i. Soft Starts, Schneider Electric brand j. HOA switches, ETMs and push button pilot lights for each pump k. Pump alternator with selector switch l. Labels for all lights, switches, pushbuttons, relays, etc….. m. 115v circuit breakers as follows: control power, condensation heater, Mission Control transformer, one spare 15 amp breaker. Owner will install Mission Control hardware in new PCP. n. Condensation Heater o. All necessary relays, to include pump over temp and seal fail, terminal blocks and, fuses. p. Auxiliary contacts for signals to RTU for Pump over temp alarm, Pump seal fail alarm, High wet well alarm, phase fail alarm, 4/20 ma flow signal q. Alarm circuitry to include the following: alarm light (Federal Signal model no. LP3P-120R, shipped loose owner will install), alarm horn (WERMA model no. 11000067 shipped loose owner will install). Alarm horn silence/reset button. |
||
Details |
|
||
Bidder's List | View project details and contacts | ||
Prospective Bidders | View project details and contacts | ||
Project Documents |
![]() Engineered Spec Sheet ![]() Architectural Plans ![]() Other Documents |