Similar Projects
Last Updated | 05/01/2020 12:14 AM |
Project Title | NKT Stadium Electrical Gear Replacement Main Switchboard |
Physical Address | View project details and contacts |
City, State (County) | Slippery Rock, PA (Butler County) |
Category(s) | Single Trades |
Sub-Category(s) | Electric |
Contracting Method | Competitive Bids. |
Project Status | Results |
Bids Due | View project details and contacts |
Estimated Value | |
Plans Available from | |
Owner | View project details and contacts |
Architect | View project details and contacts |
Description | Provide pricing for a two (2) section, 1200 amp, 480/277 VAC, 60 Hz, 3-phase, 4-wire indoor switchboard, fully-rated for a short-circuit of 25 kA. The switchboard shall include customer metering, one (1) 1200 amp 3-pole molded case main circuit breaker with LSIG electronic trip unit and arc flash reduction, one (1) UL 1449 Type 2 surge protection device, and the following thermal-magnetic molded case, 3-pole branch circuit breakers; one (1) 400 amp, one (1) 350 amp, two (2) 250 amp, one (1) 200 amp, and one (1) 100 amp. |
||
Details |
|
||
Bidder's List | View project details and contacts | ||
Prospective Bidders | View project details and contacts | ||
Project Documents |
Engineered Spec Sheet Architectural Plans Other Documents |